Standard series reactor

Series reactor
JB instead of JB 5346-5346. 5346-1998

Before the speech
This standard is according to the ministry of machine building planning revision of the standard system, in 1997, 97462002, the revised standard JB 5346-5346.
The writing of this international standard format according to the GB/T l. 1-1993 standard reorganized.
The content of the major revision of this standard are as follows:
Project 1) revised rated reactance rate by 4.8%, 6%, 12%, (13%) to 4.5%, 5%, 6%, 12%, 6%.
2) according to the requirements of form a complete set of shunt capacitance rated voltage increases the reactor of the rated voltage, and related parameters.
3) the original standard stipulated in the R10 series number system capacity of capacitor set, then rated export reactor reactance rate capacity series, purpose is to factory with as little as possible capacity to meet the requirements as much as possible the user specifications varieties.But due to the capacity of capacitor set and capacitor unit series spectrum standard is not consistent, have trouble matching combination.But even so, also cant satisfy the user needs in a wide range of specifications, so cancelled this revision in the original standard table 2 and table 3, no longer regulation capacity of the series of specifications.
4) due to cancel capacity series of specifications, also cant again to form its loss values to each kind of capacity regulation.This revision is cancelled in the original standard table 6 (A), 6, 7, 7 (A) (B) (B), 8, 8 (A) (B), loss value calculation formula is given and the loss factor.
5) reactance value allow deviation from 0 ~ 15% to 0 + 10%.
6) insulation level in line with GB 311 standard.The oil-immersed core type reactor insulation level and oil-immersed power transformer are the same, dry-type air-core reactor insulation level and busbar post insulator are the same.
7) increased use a bridge to measure reactance value content.
8) has been cancelled for outdoor type hollow reactor in heavy rain condition of winding turn-to-turn insulation test requirements.
9) to delete the clause steady-state overvoltage.Because of stable current regulation conditions, including the requirement for steady-state overvoltage, actually.
This standard by the national standardization technical committee proposed and focal points of transformer.
This standard main drafting unit: shenyang transformer research institute, ningbo transformer factory, xing-cheng special transformer factory.
In this standard drafting unit: shenyang transformer comprehensive electric co., LTD., baoding second transformer factory, Beijing electric power equipment factory, zhongshan and the electrical and mechanical plant.
The main drafter of this standard: Wang Dingyuan, Han Qingheng.
In this standard drafters: maike, GeCheng, why to see light, Shen Wenyang.
This international standard first published in 1991.In 1997 the first revision.
Shenyang transformer research institute is responsible for the interpretation of these standards.

1 scope
This standard specifies the definition of high voltage parallel capacitor in series reactor product, type and classification, technical requirements, test methods, inspection rule, the basic content of product logo and the factory documents, nameplate, the basic requirement of packaging, transport and storage, etc.
This standard applies to a category 6 ∽ 66 kv power system voltage level, in tandem with high voltage parallel capacitor group, in order to suppress the voltage waveform distortion of power grid series reactor (hereinafter referred to as the reactor).

2 reference standard
The following standards contain provision which, through reference in this text, constitute provisions of this national standard.At time of publication, the editions indicated were valid.All standards will be revised, the use of the standard of all parties should explore the possibility of applying the most recent editions of the following standards.
GB 311.1 1997 high voltage power transmission and transformation equipment insulation coordination
GB 1094.1 1996 power transformer The first part of the general (eqv IEC - 1993-76.1)
GB 1094.2 1996 power transformer The second part of temperature rise (eqv IEC - 1993-76.2)
GB 1094.3 85 power transformer The third part of the insulation level and insulation test (neq IEC - 1980-76.3)
GB 1094.5 85 power transformer The fifth part ability to withstand short circuit (neq IEC - 1976-76.5)
GB/T 5273-85 transformer, high voltage electrical and casing terminals (neq IEC 518-1975)
GB 6450-86 dry type transformer (eqv IEC 726-1982)
GB/T 6451-1995 three-phase oil-immersed power transformer technical parameters and requirements (neq DIN 42500-1984)
GB/T 7328-87 transformer and reactor sound level measurement (neq IEC 551-1976)
GB/T 10237-88 power transformer insulation level outside insulation and insulation test of air gap
(neq IEC 76-3-1-1987)
JB/T 3837-1996 transformer product model establishment method

3 define
The following definitions apply to this standard.
3.1 the rated voltage
The loop reactor in series with parallel capacitor group access to the rated voltage of the power system.In Ucn said.
Rated voltage of 3.2
Reactor with rated power-frequency electric current, a round at the ends of the phase voltage square root value of phase.With the Un said.
3.3 the rated current
With the reactor in series of the rated current of capacitor group.Use In said.
3.4 the rated capacity
Reactor in rated power-frequency voltage up to and rated current of the apparent power.Using Sn said.
The rated capacity of single phase reactor is Sn = Un, In
The rated capacity of three-phase reactor Sn = 3 UN In
3.5 the rated reactance
Reactor reactance by rated power-frequency current value.Expressed in Xn.
3.6 the rated reactive rate
Rating of the reactor reactance percentage of form a complete set of parallel capacitor group of reactance.With K said.
3.7 maximum working current
Temperature rise shall not exceed the specified value, the reactor can run continuously the maximum working current party root.
3.8 the biggest short-time current
Within the prescribed period of time to allow through the reactors biggest square root value of short-time current steady-state component.In this condition, the reactor should be able to sustain the have a dynamic and thermal stability of effect and no damage.
3.9 supporting parallel capacitor group
Rated voltage corresponding to the calculation of reactor and accord with the rated reactive rate of parallel capacitor group (hereinafter referred to as the capacitor group).
3.10 oil-immersed core reactor
Immersed in the core and winding insulation oil, core column reactor containing non magnetic gap.
3.11 the dry hollow reactor
Winding dont immersed in the insulating liquid and no core column reactor.
4 reactor models and classification
4.1 model
The reactor model according to the provisions of the JB/T 3837.
4.2 classification
2 oil-immersed core reactor.
4.2.2 dry-type air-core reactor.


[NextPage] 5 technical requirements
5.1 conditions of use
5.1.1 normal conditions of use
Oil-immersed core reactor according to the provisions of GB 1094.1.
Dry-type air-core reactor indoor type according to the provisions of GB 6450.According to the provisions of GB 1094.1 outdoor type.
5.1.2 the special conditions of use
User to be put forward in the inquiry and order article 5.1.1 in normal conditions of use of this standard does not include, the conditions of its rating and test additional requirements shall be separately agreed on.
5.2 rating
5.2.1: rated frequency 50 hz
5.2.2 phase: single phase or three phase.
5.2.3 requires rated voltage: 6, 10, 35, 66 kv.
5.2.4 rated reactance rate: 4.5%, 5%, 6%, 12%, 6%.
5.2.5 rated voltage across them
The rated voltage of calculated by (1) of the following:
Un=K·N·Ucn…………………………………………………(1)
Type: K - rated reactance rate;
N - capacitor in series per phase sets;
Ucn - supporting rated voltage parallel capacitor, kV.
Rated voltage of reactor and the related parameters should comply with the provisions of the table 1.
Table 1
The system rated voltage
kV
Form a complete set of capacitor
The rated voltage
kV
Each phase capacitor
Serial number
The reactor is the rated voltage of kV
4.5%
5%
6%
12%
13%
6
6.6 /
1
1
0.171
0.191
0.229

7.2 /



0.499
0.540
10
11 /
0.286
0.318
0.381


12 /



0.831
0.900
35
11
2
0.990
1.100
1.320


12



2.880
3.120
66
20
1.800
2.000
2.400


22



5.280
5.720
5.2.6 rated capacity
Rated capacity of three-phase reactor is calculated by (2) of the following: